Double Check Valve Assembly (DCVA) Backflow Preventer       
            Install - Maintaing - repair
          Double  Check Valve Assembly: Inline (Underground) Installation
          Before installation begins, run the main irrigation supply line from the  isolation valve to the vicinity of the DCVA valve box. Temporarily seal the end  of the pipe to keep out soil and debris. 
          
                            
                              - 
                                
Begin by installing a rectangular irrigation box in accordance with local code.  Typically, a hole at least 30" deep and 3" larger at 18” depth than  the dimensions of the valve box, centered with the trench, is filled with  enough drain rock to provide a flat surface 18" below grade. The rock is  then be covered with landscaping mesh before the rectangular valve box is set  and held in place by packing soil on two sides away from the inlet and outlet  holes. The remaining two sides are packed after the assembly is installed. 
                               
                              - 
                                
If necessary, cut inlet and outlet holes in the valve  box where needed. The hole should be no more than 1/4” larger diameter than the  pipe. 
                               
                              - 
                                
 Examine the double check valve assembly to determine which end is inlet and  which is outlet. It should be stamped with arrows. Do not proceed until  certain. 
                               
                              - 
                                
 Find the clearance from the interior of the valve box to the first fitting. Dry  fit the assembly, unions, hose bib tee, and all connecting pipe. Measure the  interior length of the valve box between the inlet and outlet holes. Subtract  the assembly length from the interior length and divide the result in half.  This is the distance from the interior upstream side of the valve box to the  first fitting. Place the dry-fitted assembly into the box to be sure there is  enough clearance for the ball valve handles in the open and closed positions.  Adjust the distance from the side of the valve box if necessary. 
                               
                              -                                 Run the supply line into the box and cut it to length as determined above. 
 
               
             
           If the double check valve assembly has built-in unions between the shutoff  valves and interior body: 
          
            
              -  Open the isolation valve to flush the main supply line thoroughly. Close the  isolation valve and dry the end of the pipe. Using thread sealant compound,  tighten a Slip X MIP adapter into the inlet shutoff valve of the double check  valve assembly. Glue or solder the adapter to the supply line positioned so  that the test cocks are on top. 
 
              -  Tighten the second Slip X MIP adapter into the outlet shutoff valve. Glue or  solder the connecting piece, a tee with a 1/2” outlet turned upwards, and  another length of pipe (long enough to exit the box) in line.
 
              - Glue or solder a short riser into the tee and install the hose bibb on top of  the riser positioned so that an air hose can easily be connected to the hose  threads. Skip the following instructions for installing unions.
 
             
             
          If  double check valve assembly does not have built-in unions between the  shutoff valves and interior body: 
          
            
              - 
                
It will be necessary to keep pipe sections as short as possible in this  installation to fit everything in the valve box. Just remember that the  shortest length of pipe must be double the length of the fitting hub plus  one-half inch so that when the connection is complete some pipe will be  visible. 
               
              - 
                
                Glue or solder the first union to the main supply inside the valve box taking  care to remove any any thread sealant compound on the interior of the pipe and  fitting. 
               
              - 
                
 Open the isolation valve to flush the main supply line thoroughly. Close the  isolation valve and dry the end of the union. 
               
              - 
                
 Tighten both Slip X MIP adapters into the inlet and outlet shutoff valves. Wipe  away any excess compound inside the fitting or valve.  
               
              - 
                
 Separate the union. Apply compound to the threads and re-tighten hand tight.  Glue or solder a short piece of pipe between the union and the assembly. Allow  to dry or cool. 
               
              - 
                
 Glue or solder a short piece of pipe into the adapter on the outlet shutoff  valve and then the second union onto the end of the pipe. Separate the union,  apply compound, and hand tighten. 
               
              - 
                
 Glue or solder the connecting piece, a tee with a 1/2” center outlet turned  upwards, and another length of pipe (long enough to exit the box) in line. Glue  or solder a short riser into the tee and install the hose bibb on top of the  riser positioned so that an air hose can easily be connected to the hose  threads.  
               
              - 
                
 When the entire assembly is straight in line and the test cocks are properly  positioned on top, tighten the unions with a wrench. 
               
              - 
                
Protect the open end of the supply with a temporary cap or plug. Seal any holes  in the valve box from the outside with duct tape to keep dirt out, and pack  soil around the valve box with a mallet. 
               
              - 
                
 Following the manufacturer's instructions, test the assembly for leaks. Then  call for inspection if required. 
               
              - 
                
 Lastly, put all written materials that came with the double check valve  assembly in a safe place for future use. 
               
             
           
          Double Check Valve Assembly: Above Ground Installation
          The steps for installing a double check valve assembly overhead in an interior  space are the same as for an inline (underground) installation except that  access is provided differently, If the assembly is installed overhead, it  should be located where nothing will be placed below it—no furniture, stacks of  boxes, vehicles, etc. A person should be able to enter the room or space and  close the shutoff valves within a matter of seconds without stopping to move  anything or locate a ladder. Also, if the backflow prevention device is located  inside a dwelling, it's a good idea to consult a local inspector regarding  Americans with Disabilities accessibility standards. 
          
             To install the double check valve assembly above ground outdoors: 
            
              - 
                
Run PVC from the isolation valve to the double check valve assembly location  indicated on the site plan. Open the isolation valve and flush the line  thoroughly. 
               
              - 
                
 Glue an elbow turned upward onto the supply line. Allow solvent cement to dry.  Measure, cut, and glue a length of PVC long enough to extend from the elbow on  the supply line to at least twelve inches above grade. The vertical pipe should  be plumb. 
               
              - 
                
 Prepare the double check valve assembly. Tighten Slip X MIP adapters into each  shutoff valve using thread sealant compound. Glue three-inch lengths of PVC  pipe and then elbows turned down into each adapter. The assembly text cocks  should be on top when the elbows are pointed down.  
               
              - 
                
 Dry-fit the the rest of the loop before gluing. Connect the elbow on the  upstream (inlet) end of the assembly to the riser on the supply line. Cut,  measure, and assemble a length of pipe extending from the downstream end of the  assembly to the bottom of the trench leaving enough room for an elbow at the  bottom. Add the final elbow and a six-inch length of pipe to continue the  supply line on the downstream side of the double check valve assembly. When  everything is aligned and plumb, disassemble and then reassemble with glue.  
               
              - 
                
 If the double check valve assembly does not have built-in union connections,  cut the vertical pipes on the inlet and outlet side about four inches below the  assembly. Separate the unions, apply thread sealant compound, and hand tighten.  Reconnect the double check valve assembly to the loop by gluing the unions in  place. With everything aligned properly, wrench-tighten the unions. 
               
              - 
                
 With both unions and the assembly now installed, the next step is to provide a  hose bibb. Glue a six-inch length of pipe, and then a riser tee with a  half-inch outlet (usually a 1 X 1 X 1/2 tee) onto the supply line.  
               
              - 
                
 Measure, cut, and glue a length of pipe long enough to extend four inches above  the ground into the center opening in the tee and then glue a mail adapter on  top. Using thread sealant compound, tighten an FIP hose bibb onto the riser.  This hose bibb will be necessary to drain the system for winterization or  repair. 
               
              - 
                
 This installation can be done using copper pipe and fittings if the homeowner  has the soldering equipment and skill. Otherwise, PVC installed as described  above is legal and adequate in most jurisdictions. If copper pipe and fittings  are used, transition to plastic after the hose bibb. Copper provides no  advantages downstream from the hose bibb. 
               
              - 
                
 Following the manufacturer's instructions, test the assembly for leaks, then  call for a backflow inspection if required. 
                     
                    NOTE: When installed outdoors, the double check valve assembly must be  enclosed. Removable covers are usually permissible. The last step in the  installation procedure is to put all printed materials in a safe  easy-to-remember location along with other irrigation literature. It will be  needed in the future. 
               
             
           
          Double Check Valve Assembly: Maintenance 
          As part of the annual winterization and maintenance of the underground  irrigation system valves, once the irrigation system isolation valve has been  closed and lines have been blown out, open all the valves on the double check  valve assembly halfway and clean out any debris from the valve box or  enclosure. If the double check valve assembly is indoors, make sure access is  still clear when the system is reactivated in the spring.  
               
            Have the assembly tested and inspected in accordance with local code.  Scheduling inspections just before reactivating the system in the spring will  get the season off to a good start. 
               
            Every five years, have internal non-metallic parts replaced and inspect  internal metal parts for possible replacement. SprinklerWarehouse.com has  replacement parts for all major brands of double check valve assemblies. 
          
            
              Double Check Valve Assembly: Repair
                Each double check valve assembly comes with explicit instructions for  maintenance and repair. Rubber components check modules, and seals can be  replaced by a mechanically competent homeowner or plumber (if allowed by local  code). Many jurisdictions require that any time the access cover is opened for  any reason or the assembly is disconnected from the system, it must be tested  by a state-certified backflow assembly inspector before being put back into  service.  
                     
                  Replacement is rarely ever necessary. Replacing the entire double check valve  assembly with a new one is a fairly simple process. Disconnect the assembly section  at the unions, and duplicate the section using a new double check valve  assembly, pipe, and fittings. Then reconnect, test for leaks, and call for  inspection if required. 
   
                  It must be noted, though, that jurisdictions around the country have been proscribing  double check valve assembly or specific installation configurations recently.  Once the entire original double check valve assembly is discarded, any  “grandfather” protection is probably lost. If double check valve assemblies  have been proscribed locally since it was installed, it may have to be replaced  with a new pressure vacuum breaker or reduced pressure assembly. Check with  local authorities before purchasing a replacement double check valve assembly.   | 
               | 
             
           
                     
  |